Building The Future,Restoring The Past
Individually Assess Each Plan &
Offer Optimal Solutions!
Home > Product Details
Product Category
Solar Energy
CONTAINERIZED HYBRID SOLAR INVERTER POWER SYSTEM 10KW~400KW
Category: Solar Energy
Summarize
This specification established the highway project requirement for a solar system for local conditions in Pakistan.
Technical specification of solar system sets:
General:
The proposed solar system should be completed with all necessary and compatible with Pakistan climate conditions with the following technical specifications. Also including the solar panel's installation.
The TYN series of the hybrid solar power supply systems is a set of photovoltaic solar modules, intelligent photovoltaic converters, photovoltaic control systems, photovoltaic inverter systems, lead-acid batteries, communication control systems, air conditioning systems, and backup generators With the composition of the large-scale photovoltaic energy storage system. The power supply system mainly uses photovoltaic power generation, battery storage, when the inverter system failure or battery power exhaustion starts generator power supply. A new generation of green power solutions.
A.Solar Inverter:
BK-TYN-33-40KVA 2PCS
BK-TYN-33-60KVA 4PCS
BK-TYN-33-100KVA 1PCS
Solar System Working Principle
TYN Series is an intelligent multi-function solar inverter, consist of an MPPT solar Controller (high-power MPPT Controller external installation), charger, rectifier, inverter, static switch, main control circuit and display alarm circuit, and so on. According to the user’s actual application, as you can set different mode:
1.PV– Gird– Battery: This series PV inverter design for photovoltaic(PV) and Grid sharing function, solar priority, photovoltaic through the MPPT controller supply to the inverter, and outputs a pure sine AC to loads, meanwhile charging the battery pack; When the solar is not enough to supply the load, it is supplemented by the grid power; utmost use solar energy and grid power, to reduce battery discharge, external battery life span.
2.PV-Battery-Grid (if grid stable, utmost use solar energy): photovoltaic through the MPPT controller supply to the inverter, after inverter output pure sine AC to the loads, meanwhile charging the battery pack; When the solar power is not enough to power the load and to utmost use solar energy, photovoltaic not enough to output power from the battery for replenishing, discharging the battery a little bit, and then switch to the grid supply; maximum utilize photovoltaically, to save electric bill.
B.20” container
Custom-made 20″ container, external spray BAYKEE logo, internal fixed position, hole, etc.Internal position design and fixed reinforcement.
Plane layout:
C. Solar Panels
Poly-crystalline,265W
BK-TYN-33-40KVA-SYS 108PCS
BK-TYN-33-60KVA-SYS 144PCS
BK-TYN-33-100KVA-SYS 234PCS
D. PDU
BK-PD-40KVA 1PCS
BK-PD-60KVA 1PCS
BK-PD-100KVA 1PCS
E. Maintenance Free Lead Acid Battery
BK-TYN-33-40KVA-SYS JFM-2V-300AH 192PCS
BK-TYN-33-60KVA-SYS JFM-2V-300AH 192PCS
BK-TYN-33-100KVA-SYS JFM-2V-600AH 192PCS
F. Battery Rack
C300-192(64*3) 3ets
G. Light LED 20W
BK-TYN-33-40KVA-SYS 4PCS
BK-TYN-33-60KVA-SYS 4PCS
BK-TYN-33-100KVA-SYS 4PCS
H. Fire Extinguisher
Dry powder fire extinguisher
BK-TYN-33-40KVA-SYS 2PCS
BK-TYN-33-60KVA-SYS 2PCS
BK-TYN-33-100KVA-SYS 2PCS
I. Exhaust Fan
BK-TYN-33-40KVA-SYS 1PCS
BK-TYN-33-60KVA-SYS 1PCS
BK-TYN-33-100KVA-SYS 1PCS
J. Wire/Cable
BK-TYN-33-40KVA-SYS cable1:25m㎡ 55 meters cable2: 4m㎡ 350 meters
BK-TYN-33-60KVA-SYS cable1:35m㎡ 55 meters cable2: 4m㎡ 450 meters
BK-TYN-33-100KVA-SYS cable1:70m㎡40 meters cable2: 50m㎡20meters cable 3:4m㎡ 800meters
Type | Input | Output | PV of each | Battery | |||||
A、B、C | N | PE | A、B、C | N | + | – | + | – | |
TYN33-10K | 6 | 6 | 4 | 6 | 6 | 16 | 16 | 10 | 10 |
TYN33-20K | 10 | 10 | 6 | 10 | 10 | 16 | 16 | 16 | 16 |
TYN33-30K | 16 | 16 | 6 | 16 | 16 | 16 | 16 | 25 | 25 |
TYN33-40K | 25 | 25 | 10 | 20 | 20 | 16 | 16 | 35 | 35 |
TYN33-60K | 35 | 35 | 10 | 25 | 25 | 16 | 16 | 50 | 50 |
TYN33-80K | 50 | 50 | 16 | 35 | 35 | 16 | 16 | 70 | 70 |
TYN33-100K | 60 | 60 | 25 | 50 | 50 | 16 | 16 | 80 | 80 |
TYN33-120K | 70 | 70 | 35 | 60 | 60 | 16 | 16 | 90 | 90 |
Type | Input switch | Output switch | PV switch of each | Battery switch |
TYN33-10K | 32A-3P | 32A-3P | 63A-2P | 50A-2P |
TYN33-20K | 50A-3P | 50A-3P | 63A-2P | 100A-2P |
TYN33-30K | 63A-3P | 63A-3P | 63A-2P | 125A-2P |
TYN33-40K | 100A-3P | 100A-3P | 63A-2P | 175A-2P |
TYN33-60K | 150A-3P | 125A-3P | 63A-2P | 225A-2P |
TYN33-80K | 175A-3P | 175A-3P | 63A-2P | 225A-2P |
TYN33-100K | 200A-3P | 200A-3P | 63A-2P | 300A-2P |
TYN33-120K | 225A-3P | 225A-3P | 63A-2P | 400A-2P |