BKH Brief
BKH series modularized UPS maintains the technical features of traditional tower-type UPS and adopts modularized design to meet the need of modern service room, while ensuring the high reliability of the system. BKH series offers various power modules and cabinet systems, and the user can able to flexibly combine them according to load demand. The capacity of a single cabinet is 200KVA and that of combined cabinets reaches 400KVA.
BKH Main Features
- UPS system is modular design, N+X redundancy, hot plugging for system update or capacity expansion
- Strong load adaptability and loading capacity, and excellent power grid applicability
- Green and energy-saving power supply; overall efficiency>95%, input power factor> 0.99, input current harmonics (THDi) <3%
- Dual DSP for independent control of power module, no single point of failure
- Digital control of rectification, inverter, charging and discharging via DSP
- Integrated and packaged IGBT instead of discrete device to greatly enhance the reliability of power module and UPS system
- Front panel for easy maintenance, inlet wire from top to bottom for easy connection by user
- Large touch screen of human-machine interface, a great amount of information
- Independent charging system, strong charging capacity, Perfect battery management scheme
- Parallel connection technology of digital modules, precision circular current index
- Easy to install even close to other equipments, space-saving footprint in service room
- Redundancy and intelligent adjustable-speed fan, low noise, low power consumption
- Integrated distribution system inside system cabinet, easy to install, low investment by user
- Good matching performance with motor
- DC Starting via battery (cold boot) for easy operation
- Three-proofing treatment of all circuit boards.
- Optional Standard battery bank or extension battery bank
Capacity (KVA) | 1-200KVA | ||
---|---|---|---|
Main Input | |||
Phase | |||
Input Voltage | 380V/400V/415V | ||
Input Frequency | 50/60Hz | ||
Power Factor | >0.99 | ||
Input Total Harmonic Distortion | THDi<3% | ||
Input voltage Range | -40%~+C1125% | ||
Frequency Range | 40-70Hz | ||
Battery | |||
Battery Voltage | ±240VDC or ±384VDC | ||
Charger Power | 20% * System Power | ||
Charger Voltage Precision | 1% | ||
Bypass | |||
Bypass Voltage | 380V/400V/415V | ||
Bypass Voltage Range | -50%~+20% | ||
Overload Capability | 150%<load<180%, time=”” work=””>1mins, >180%, work time< 100ms</load<180%,> | ||
Output | |||
Output Voltage | 380V/400V/415V | ||
Output Voltage Regulated Accuracy | ±1%( Stable load ), ±3%( fluctuant load ) | ||
Total Harmonic Distortion | THD<1% ( Linear Load ), THD< 3% ( Non-Linear Load ) | ||
Output Power Factor | 0.8 | ||
Crest Factor | 3:01 | ||
Overload Capability | 125%, switch to bypass after 10H, 150%, switch to bypass after 1H, >150%, switch to bypass after 200ms | ||
System Parameters | |||
System Efficiency | Normal Mode: 95%, ECO Mode: 99% | ||
Battery Mode Efficiency | 95% | ||
Display | LCD+LED, Touch Screen+ Keyboard | ||
Protection Level | IP20 | ||
Communication Port | RS232, RS485, Dry contacts, SNMP card, EPO, Generator port | ||
Connection method | Support connection of up and down | ||
Running temperature | 0-40ºC | ||
Storage temperature | -25ºC-70ºC | ||
Relative humidity | 0-95% ( no condensing ) | ||
Noise (dB) | <55dB | ||
Weight (Kg) | 6-module cabinet | Model: BKH060K/10, BKH090/15, BKH120/20 | 150Kg |
10-module cabinet | Model: BKH100K/10, BKH150/15, BKH200/20 | 180KG | |
Model: PM10 | 10kVA power module: 20Kg | ||
Model: PM15 | 15kVA power module: 21Kg | ||
Model: PM20 | 20kVA power module: 22Kg | ||
Size ( W*D*H ) mm | 6-module cabinet | 600*900*1600 | |
10-module cabinet | 600*900*2000 | ||
Power module | 440*600*134 ( 10KVA/15KVA/20KVA ) |